Product Overview
Product Details
Data Download
Related Products
Contact Us
Rated insulation voltage AC690V, rated frequency 50Hz, rated operating current 0.5A~300A.
| Model Parameter |
JD-5 | JD-5B (with buzzer) |
JD-6 | BHQ-S-C | BHQ-S-J | |
| Rated voltage | AC380V 50Hz(Other voltage levels can be customized) | |||||
| Setting current range(suitable motor power) | 2-100A(1-40KW) | 2-100A(1-40KW) | 60-400A(30-150KW) | 2-100A,63-150A,100-250A | 0.5-5A,5-20A | |
| Overload action time (with inverse time limit characteristics) |
3-300s(Adjustable) | |||||
| Phase failure action time | ≤2s | |||||
| Reset mode | De-energizing reset | |||||
| Contact capacity | AC380V 3A | |||||
| Display mode Alarm mode |
LED Light indication Sound-light alarm |
|||||
| Mechanical life | 106 | |||||
| Electric life | 105 | |||||
| Installation mode | Screw | |||||
Operation characteristics under three-phase balanced-load status
| I/In | Operating time | Test condition | Ambient temperature | |||||||||||||||||||||
| 1.05 | <2h non-tripping | Cold status | +20℃ | |||||||||||||||||||||
| 1.20 | <2h tripping | Heat status | ||||||||||||||||||||||
| 1.50 | <2 min tripping | Heat status | ||||||||||||||||||||||
| 7.20 | 2s<Tp≤10s | Cold status | ||||||||||||||||||||||
Operation characteristic under phase-failure status
| Multiple of setting current | Operating time | Test condition | Ambient temperature | ||||||||||||||||||||
| Any two phases | The third phases | ||||||||||||||||||||||
| 1.0 | 0.9 | <2h non-tripping | Cold status | +20℃ | |||||||||||||||||||
| 1.15 | 0 | ≤5s | Heat status | ||||||||||||||||||||